Recommended Cleat Spacings

图150图示出了根据固定中心/间隔所需的每个电缆夹板所需的拉伸强度。

= 0.17/ S
= maximum force on the cable conductor (N/m)

0.17(190 x 190)/(36/1000)= 170,477.22 n / m
电缆Ø= 36mm= 190kA
mounting intervals: 300mm (x 0.3) = 51,141.67N per cable cleat

0.17(190 x 190)/(36/1000)= 170,477.22 n / m
电缆Ø= 36mmCable Cleat Spacing Calc= 190kA
mounting intervals: 600mm (x 0.6) = 102,283.33N per cable cleat.
这种配置中的每个电缆夹板必须抑制力量的两倍
在上述配置(300mm)中的那些。

0.17(190 x 190)/(36/1000)= 170,477.22 n / m
电缆Ø= 36mm= 190kA
mounting intervals: 900mm (x 0.9) = 153,424.00N per cable cleat.
Each cable cleat in this configuration must restrain one-and-a-half times the force of those in the above
configuration (600mm), or three times the force of those in the first configuration (300mm).